تخطي الروابط
FLE-VQ-F · Electric V-Port Control Valve

مشغل كهربائي لصمام كروي من النوع V | FLE-VQ-F

The FLE-VQ-F electric actuated V-port ball valve is designed for proportional flow control where a standard round-port ball valve does not provide enough usable control range. A characterized V-notch opening creates a progressive change in flow area as the segmented ball rotates, supporting stable modulation of water, steam, gas, slurry, pulp and compatible process liquids.

15° / 30° / 60° / 90° V-Port Options Modulating Electric Actuator Flanged ANSI / DIN / JIS PLC / DCS Integration
Email Our Engineers
inquiry@fleyendaflow.com
Size
DN25–DN300
الضغط
PN16–PN40
درجة الحرارة
Up to +250°C*
Control
Modulating / Intelligent
FLE-VQ-F V port ball valve with electric actuator for modulating flow control
Precision control focus

Built around the V-notch geometry first, then matched with the electric actuator required for the control loop.

4V-port angle options: 15°, 30°, 60°, 90°
0–90°Quarter-turn actuator travel
4–20 mASelected modulating control configurations
Why V-port control

More usable valve travel for proportional flow control

A conventional round-port ball valve is excellent for isolation, but its flow area changes too quickly for many throttling duties. The V-shaped opening changes the effective flow area more progressively as the ball rotates.

This gives the electric actuator more usable positioning range for dosing, feed-flow regulation, temperature loops and variable process demand. The segmented V-ball also creates a shearing action at the seat, which can help reduce buildup in selected slurry, pulp and particle-bearing services.

  • 01Fine-position control. Better use of actuator travel at partial openings.
  • 02Process stability. Suitable for PLC / DCS loops that make frequent position corrections.
  • 03High flow capacity. V-port options can be matched from fine regulation to higher-Cv duties.
  • 04Media flexibility. Water, steam, gas, oil, pulp, slurry and compatible chemical liquids.
Need help selecting a V-port angle?Send the medium, flow range, pressure drop and pipe size.
Ask About V-Port Selection
Industrial process control system using electric V port ball valve for proportional flow regulation
Closed-loop process controlElectric V-port ball valves for stable modulation in automated process systems.
Technical data

FLE-VQ-F V-port segmented ball valve specifications

The valve body, seat, V-port geometry and actuator should be selected as one control assembly based on the real process conditions.

Product typeElectric actuated V-port segmented ball valve / motorized V-port control ball valve
Size range1″–12″ / DN25–DN300
ضغط التشغيلPN16–PN40 / ANSI Class 150–300
Working temperature−20°C to +250°C, depending on seat material and service conditions
Body materialالفولاذ المقاوم للصدأ CF8 / CF8M / الفولاذ الكربوني WCB
Seat optionsPTFE or selected metal-seat configurations
V-port options15°, 30°, 60°, 90°
الاتصالFlanged — ANSI / DIN / JIS options
Applicable mediaWater, steam, gas, oil, slurry, pulp and compatible chemical liquids
ActuationElectric quarter-turn actuator; on/off, regulating and intelligent configurations
Voltage options24 فولت تيار مستمر، 24 فولت تيار متردد، 110 فولت تيار متردد، 220 فولت تيار متردد، 380 فولت تيار متردد
Control optionsOn/off, selected 4–20 mA regulating control, feedback and intelligent configurations
Design referencesIEC 60534 / GB/T 12237 / API 6D
الاختبارAPI 598 / EN 12266-1
Fire-safe optionSelected API 607 configurations available
ProtectionIP67 standard on selected actuators; IP68 optional
Explosion-proof optionSelected Ex d II BT4 / CT4 / CT6 Gb actuator configurations
Send your flow-control conditions for sizing.Include minimum / normal / maximum flow, pressure, temperature, medium and control signal.
Send Control Data by Email
V-port selection

Choose the V-notch around the required control duty

Different V-port openings shift the balance between fine regulation and flow capacity. Final selection should be based on Cv demand, pressure drop, media and the usable control range required by the loop.

15°Fine regulationUseful where small changes in opening must produce controlled changes in flow.
30°Low-to-medium flow dutyBalances controllability with additional capacity for dosing and process feed service.
60°Broader control rangeSuitable for many general modulating applications requiring more available flow.
90°Higher-Cv requirementSelected where higher flow capacity is required while retaining V-port modulation.
Do not choose the V-port angle from pipe size alone.Share flow rate and pressure-drop data so the valve can be sized around the actual operating point.
Ask for Cv Selection
Control valve comparison

V-port ball valve vs standard round-port ball valve

Both are quarter-turn valves, but they solve different process problems. The V-port version is selected when proportional control is the primary duty.

Selection factor
V-port electric ball valve
Standard round-port electric ball valve
Main function
Proportional / modulating flow control
Isolation, open / close service
Opening geometry
Characterized V-notch / segmented ball
Conventional circular bore
Partial opening
Designed to provide more usable control travel
Flow can change rapidly through part of the travel
Typical signals
4–20 mA or selected intelligent modulating control
On/off command and optional position feedback
Typical duty
Dosing, feed-flow, steam, slurry, temperature and process loops
Pipeline isolation, equipment switching and shutoff
Electric actuator & control

Match actuator torque, signal and duty cycle to the control loop

For a V-port control valve, actuator selection is not only about opening and closing torque. Positioning accuracy, feedback, operating frequency and control architecture also affect loop performance.

التحكم التعديليSelected 4–20 mA and intelligent actuator configurations.
تغذية الارتجاع للموضعFeedback options for PLC / DCS monitoring and closed-loop control.
On / OffAvailable where the same V-port body is used for automatic switching duty.
مصدر الطاقةDC24V, AC24V, AC110V, AC220V and AC380V options.
ProtectionIP67, optional IP68 and selected explosion-proof configurations.
Fail PositionSelected fail-open, fail-closed and related safety options.
المشغلStandard time / torqueOptional time / torqueالوزن
FLE-10525s / 50Nm4s / 20Nm; 10s / 30Nm2.2 كجم
FLE-11025s / 100Nm15s / 50Nm5.1 كجم
FLE-11625s / 160Nm15s / 80Nm5.1 كجم
FLE-12025s / 200Nm15s / 100Nm7.5 كجم
FLE-14025s / 400Nm15s / 200Nm7.5 كجم
FLE-16025s / 600Nm15s / 300Nm8.1 كجم
FLE-110050s / 1000Nm25s / 500Nm12.7 كجم
FLE-120050s / 2000Nm25s / 1000Nm12.7 كجم
Need actuator sizing for modulating service?Send valve size, ΔP, media, cycle frequency, voltage and control signal.
Ask About Actuator Sizing
Application environments

Where electric V-port ball valves are typically used

The strongest fit is a process that needs repeatable throttling, remote electric actuation and more predictable control than a standard isolation ball valve can provide.

Water and wastewater treatment flow control application for electric V port ball valve
Dosing · Filtration · Flow LoopsWater & Wastewater Treatment

Modulating chemical feed, filter flow, neutralization and process-water control.

Chemical dosing and blending process application for motorized V port ball valve
Dosing · Blending · Reactor Feedالمعالجة الكيميائية

Controlled transfer and feed-flow adjustment for compatible chemical process media.

Pulp slurry industrial process application for segmented V ball control valve
Pulp · Slurry · Suspended SolidsPulp & Paper / Slurry Service

The segmented V-ball can provide a shearing action useful in selected particle-bearing process lines.

Steam and industrial utility control application for electric actuated V port ball valve
Steam · HVAC · Process UtilitiesEnergy & Utility Control

Flow and temperature-loop regulation in compatible steam, heating and plant utility systems.

Have a different control application?Email your process data for valve body, seat, V-port and actuator matching.
Discuss Your Application
Engineering selection

Size the control duty before choosing the electric actuator

A V-port valve should be selected from process data, not only nominal pipe diameter. Oversizing can leave the normal operating point at a very small opening and reduce usable control travel.

01

Define the medium

State liquid, gas, steam, slurry or pulp service, plus concentration, solids and compatibility requirements.

02

Provide the flow range

Minimum, normal and maximum flow are more useful for control-valve sizing than pipe size alone.

03

Confirm upstream / downstream pressure

Provide actual pressure drop at the main operating points so the required Cv can be evaluated.

04

Choose body, seat & V-port

Match materials and V-notch geometry to temperature, media, control range and wear conditions.

05

Match actuator torque & duty cycle

Consider valve torque, differential pressure, modulation frequency and an appropriate engineering safety margin.

06

Specify signal & feedback

Define 4–20 mA or other required control, feedback, fail position, supply voltage, IP rating and hazardous-area needs.

For faster selection, send all six items in one email.Our engineers can review the V-port valve and actuator as a complete control assembly.
Email Selection Data
Quality & protection

Industrial actuator options for continuous process environments

FLE-VQ-F assemblies can be configured around the project requirement, including selected protection, safety and electric-actuator options for industrial automation service.

API 598Valve testing reference listed for the FLE-VQ-F series.
IP67 / IP68Selected electric actuator protection options.
BT4 / CT6Selected explosion-proof actuator configurations.
Frequently asked questions

V-port ball valve electric actuator FAQs

Answers focused on modulating control, V-port selection, actuator signals and the difference between V-port and standard ball valves.

What is a V-port ball valve with an electric actuator?
It combines a V-notch or segmented ball valve with a quarter-turn electric actuator. Unlike a standard on/off ball valve, the V-shaped opening is intended to provide more usable valve travel for proportional flow control. Depending on the actuator configuration, it can be integrated with PLC or DCS systems for modulating service.
Why use a V-port ball valve instead of a standard electric ball valve?
A standard round-port ball valve is primarily optimized for isolation. A V-port ball valve changes the effective flow area more progressively as it rotates, making it better suited to dosing, feed-flow regulation, temperature loops and other processes where stable partial-opening control is important.
Which V-port angle should I choose: 15°, 30°, 60° or 90°?
The angle should be selected from the required flow coefficient, pressure drop and control range. Smaller V-notch options are generally associated with finer low-flow regulation, while larger openings provide more capacity. The correct choice should be confirmed from the real minimum, normal and maximum flow conditions.
Can the FLE-VQ-F support 4–20 mA modulating control?
Selected regulating electric actuator configurations can support 4–20 mA control and position feedback. When requesting a quotation, specify the required input signal, feedback signal, power supply, fail position and PLC / DCS interface requirements.
Can a segmented V-ball valve handle slurry or pulp?
The segmented V-ball geometry creates a shearing action at the seat and can be suitable for selected slurry, pulp and suspended-solid services. Final suitability depends on solids concentration, particle characteristics, velocity, seat material, pressure drop and wear conditions.
What information is needed to size an electric V-port control valve?
Provide the process medium, minimum / normal / maximum flow, inlet and outlet pressure, temperature, pipe size, required materials, control signal, power supply and operating frequency. These values allow the valve Cv, V-port geometry and electric actuator torque to be reviewed together.

Need a V-port valve sized around your actual flow conditions?

Send the medium, flow range, pressure drop, temperature, size, voltage and control signal for FLE-VQ-F selection.

Email inquiry@fleyendaflow.com